Program Guidelines for Open Loop Water Source Heat Pumps
Air Source Heat Pump to Open Loop Water Source Heat Pump Criteria

Equipment Qualification
- Heat pump is
- Minimum 3.5 COP as listed on the AHRI certificate
- Heat pump is 6 tons or less
- Heat pump is sized using Manual J or equivalent and capacity is within ½ ton of the calculated dominant design load (heating or cooling).
- Heat pump replaces an existing air source heat pump.
- Limited to one unit per household.
Installation Qualification
- Visually inspect ductwork; verify there are no disconnected ducts. Repair disconnect(s) before installing equipment.
- Confirm system airflow is at least 325 CFM/Ton as measured with TrueFlow® Meter.
- Confirm heat of extraction/rejection is within the manufacturer’s tolerances. Adjust charge as needed and retest.
Submit the following to Idaho Power
To avoid a delay in processing, ensure forms and worksheets are completed in full.
- Open Loop Water Source Heat Pump Incentive Application
- Open Loop Water Source Heat Pump Installation Worksheet
- Certificate of AHRI-Certified Performance
- Manual J or equivalent (such as the Idaho Power Heat Pump Sizing Worksheet). Use care in selecting the proper Entering Water Temperature when selecting equipment.
- Copy of itemized receipt/invoice
Electric Heat System to Open Loop Water Source Heat Pump Criteria

Equipment Qualification
- Heat pump is
- Minimum 3.5 COP as listed on AHRI certificate
- Heat pump is 6 tons or less
- Heat pump is sized using Manual J or equivalent and capacity is within ½ ton of the calculated dominant design load (heating or cooling).
- Heat pump replaces an existing electric heating system (i.e. furnace, baseboards, etc.) with a heat pump with electric backup.
- Limited to one unit per household.
Installation Qualification
- Visually inspect ductwork; verify there are no disconnected ducts. Repair disconnect(s) before installing equipment.
- Confirm system airflow is at least 325 CFM/Ton as measured with TrueFlow® Meter.
- Confirm suction/discharge pressures and heat of extraction/rejection is within manufacturer’s tolerances. Adjust charge as needed and retest.
Submit the following to Idaho Power
To avoid a delay in processing, ensure forms and worksheets are completed in full.
- Open Loop Water Source Heat Pump Incentive Application
- Open Loop Water Source Heat Pump Proper Installation Worksheet
- Certificate of AHRI-Certified Performance
- Manual J or equivalent (such as the Idaho Power Heat Pump Sizing Worksheet). Use care in selecting the proper Entering Water Temperature when selecting equipment.
- Copy of itemized receipt/invoice
Oil or Propane Heating System to Open Loop Water Source Heat Pump Criteria

Equipment Qualification
- Heat pump is
- Minimum 3.5 COP as listed on the AHRI certificate
- Heat pump is 6 tons or less
- Heat pump is sized using Manual J or equivalent and capacity is within ½ ton of the calculated dominant design load (heating or cooling).
- Home is located in an area where natural gas is not available.
- Limited to one unit per household.
Installation Qualification
- Visually inspect ductwork; verify there are no disconnected ducts. Repair disconnect(s) before installing equipment.
- Confirm system airflow is at least 325 CFM/Ton as measured with TrueFlow® Meter.
- Confirm heat of extraction/rejection is within manufacturer’s tolerances. Adjust charge as needed and
retest.
Submit the following to Idaho Power
To avoid a delay in processing, ensure forms and worksheets are completed in full.
- Open Loop Water Source Heat Pump Incentive Application
- Open Loop Water Source Heat Pump Proper Installation Worksheet
- Certificate of AHRI-Certified Performance
- Manual J or equivalent (such as the Idaho Power Heat Pump Sizing Worksheet). Use care in selecting the proper Entering Water Temperature when selecting equipment.
- Copy of the itemized receipt/invoice
New Construction Open Loop Water Source Heat Pump Criteria

Equipment Qualification
- Heat pump is
- Minimum 3.5 COP as listed on the AHRI certificate
- Heat pump is 6 tons or less
- Heat pump is sized using Manual J or equivalent and capacity is within ½ ton of the calculated dominant design load (heating or cooling).
- Home is constructed in an area where natural gas is not available.
- Limited to one unit per household.
- Construction must be completed and certificate of occupancy issued prior to submitting incentive
paperwork.
Installation Qualification
- Visually inspect ductwork; verify there are no disconnected ducts. Repair disconnect(s) before installing equipment.
- Confirm system airflow is at least 325 CFM/Ton as measured with TrueFlow® Meter.
- Confirm heat of extraction/rejection is within manufacturer’s tolerances. Adjust charge as needed and
retest.
Submit the following to Idaho Power
(to avoid a delay in processing, ensure forms and worksheets are completed in full)
- Open Loop Water Source Heat Pump Incentive Application
- Open Loop Water Source Heat Pump Proper Installation Worksheet
- Certificate of AHRI-Certified Performance
- Manual J or equivalent (such as the Idaho Power Heat Pump Sizing Worksheet). Use care in selecting the proper Entering Water Temperature when selecting equipment.
- Copy of itemized receipt/invoice