Program Guidelines for Open Loop Water Source Heat Pumps

Air Source Heat Pump to Open Loop Water Source Heat Pump Criteria



Equipment Qualification

  • Heat pump is
    •  Minimum 3.5 COP as listed on the AHRI certificate
  • Heat pump is 6 tons or less
  • Heat pump is sized using Manual J or equivalent and capacity is within ½ ton of the calculated dominant design load (heating or cooling).
  • Heat pump replaces an existing air source heat pump.
  • Limited to one unit per household.

Installation Qualification

  • Visually inspect ductwork; verify there are no disconnected ducts. Repair disconnect(s) before installing equipment.
  • Confirm system airflow is at least 325 CFM/Ton as measured with TrueFlow® Meter.
  • Confirm heat of extraction/rejection is within the manufacturer’s tolerances. Adjust charge as needed and retest.

Submit the following to Idaho Power

To avoid a delay in processing, ensure forms and worksheets are completed in full.

  • Open Loop Water Source Heat Pump Incentive Application
  • Open Loop Water Source Heat Pump Installation Worksheet
  • Certificate of AHRI-Certified Performance
  • Manual J or equivalent (such as the Idaho Power Heat Pump Sizing Worksheet). Use care in selecting the proper Entering Water Temperature when selecting equipment.
  • Copy of itemized receipt/invoice

 

Electric Heat System to Open Loop Water Source Heat Pump Criteria



Equipment Qualification

  • Heat pump is
    • Minimum 3.5 COP as listed on AHRI certificate
  • Heat pump is 6 tons or less
  • Heat pump is sized using Manual J or equivalent and capacity is within ½ ton of the calculated dominant design load (heating or cooling).
  • Heat pump replaces an existing electric heating system (i.e. furnace, baseboards, etc.) with a heat pump with electric backup.
  • Limited to one unit per household.

Installation Qualification

  • Visually inspect ductwork; verify there are no disconnected ducts. Repair disconnect(s) before installing equipment.
  • Confirm system airflow is at least 325 CFM/Ton as measured with TrueFlow® Meter.
  • Confirm suction/discharge pressures and heat of extraction/rejection is within manufacturer’s tolerances. Adjust charge as needed and retest.

Submit the following to Idaho Power

To avoid a delay in processing, ensure forms and worksheets are completed in full.

  • Open Loop Water Source Heat Pump Incentive Application
  • Open Loop Water Source Heat Pump Proper Installation Worksheet
  • Certificate of AHRI-Certified Performance
  • Manual J or equivalent (such as the Idaho Power Heat Pump Sizing Worksheet). Use care in selecting the proper Entering Water Temperature when selecting equipment.
  • Copy of itemized receipt/invoice

     

Oil or Propane Heating System to Open Loop Water Source Heat Pump Criteria



Equipment Qualification

  • Heat pump is
    •  Minimum 3.5 COP as listed on the AHRI certificate
  • Heat pump is 6 tons or less
  • Heat pump is sized using Manual J or equivalent and capacity is within ½ ton of the calculated dominant design load (heating or cooling).
  • Home is located in an area where natural gas is not available.
  • Limited to one unit per household.

Installation Qualification

  • Visually inspect ductwork; verify there are no disconnected ducts. Repair disconnect(s) before installing equipment.
  • Confirm system airflow is at least 325 CFM/Ton as measured with TrueFlow® Meter.
  • Confirm heat of extraction/rejection is within manufacturer’s tolerances. Adjust charge as needed and
    retest.

Submit the following to Idaho Power

To avoid a delay in processing, ensure forms and worksheets are completed in full.

  • Open Loop Water Source Heat Pump Incentive Application
  • Open Loop Water Source Heat Pump Proper Installation Worksheet
  • Certificate of AHRI-Certified Performance
  • Manual J or equivalent (such as the Idaho Power Heat Pump Sizing Worksheet). Use care in selecting the proper Entering Water Temperature when selecting equipment.
  • Copy of the itemized receipt/invoice

     

New Construction Open Loop Water Source Heat Pump Criteria



Equipment Qualification

  • Heat pump is
    •  Minimum 3.5 COP as listed on the AHRI certificate
  • Heat pump is 6 tons or less
  • Heat pump is sized using Manual J or equivalent and capacity is within ½ ton of the calculated dominant design load (heating or cooling).
  • Home is constructed in an area where natural gas is not available.
  • Limited to one unit per household.
  • Construction must be completed and certificate of occupancy issued prior to submitting incentive
    paperwork.

Installation Qualification

  • Visually inspect ductwork; verify there are no disconnected ducts. Repair disconnect(s) before installing equipment.
  • Confirm system airflow is at least 325 CFM/Ton as measured with TrueFlow® Meter.
  • Confirm heat of extraction/rejection is within manufacturer’s tolerances. Adjust charge as needed and
    retest.

Submit the following to Idaho Power

(to avoid a delay in processing, ensure forms and worksheets are completed in full)

  • Open Loop Water Source Heat Pump Incentive Application
  • Open Loop Water Source Heat Pump Proper Installation Worksheet
  • Certificate of AHRI-Certified Performance
  • Manual J or equivalent (such as the Idaho Power Heat Pump Sizing Worksheet). Use care in selecting the proper Entering Water Temperature when selecting equipment.
  • Copy of itemized receipt/invoice